Electrical panel ground/neutral bus bar question

In CH type panel CMBE4242B200BTS ( main bus is Copper) , I am trying to replace AL ground/neutral bus bar with copper bus.

The current Ground/Neutral bus in the panel is Tin plated Aluminum ( 6061-T6).
All my wiring is copper. Do you guys see any issues with this ?

Thanks
Diwakar
Attached Images
 
Electrical panel ground/neutral bus bar question

2 commentaires:

  1. Réponses
    1. Yes you must change the two bars for copper bars , the panel was designed for work with aluminun wire ,the main bus bar are copper ;an the breakers for this panel shall be AL/CU .or CU only so you got copper wiring .