I have a single 14X7 plenum / main trunk running off of my furnace which serves 6 6" branches terminating with 6X10 registers. From what calculators I can find online, it seems that trunk is maxed out. Does my "math" sound right to you? Also, does this seem inadequate for a 60K BTU 95% 2 stage furnace?
Anyhow, high delta T readings on my new 60K 95% 2 stage suggest I'm not moving enough air with this system. Seeing as I need a 4 more registers and have the room to work in another trunk off of the plenum, I figure this could fix my issues...
Am I on the right track here? Thanks!
FWIW, stage 1 delta T's have hit as high as 68 and 1&2 has hit 84.
Furnace specs:
Delta T S1 at 30-60 and S1&2 45-75
Stage 1 CFM 775
Stage 2 CFM 940
A/C CFM 1090
Opening to plenum 12.5" X 19.125"
Anyhow, high delta T readings on my new 60K 95% 2 stage suggest I'm not moving enough air with this system. Seeing as I need a 4 more registers and have the room to work in another trunk off of the plenum, I figure this could fix my issues...
Am I on the right track here? Thanks!
FWIW, stage 1 delta T's have hit as high as 68 and 1&2 has hit 84.
Furnace specs:
Delta T S1 at 30-60 and S1&2 45-75
Stage 1 CFM 775
Stage 2 CFM 940
A/C CFM 1090
Opening to plenum 12.5" X 19.125"